Governor Model: URGS3T
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Linc < 0.25*Mult*TimeStep then Linc = 0.0
ElseIf 0.25*Mult*TimeStep < Linc < 0.5*Mult*TimeStep then Linc = 0.5*Mult*TimeStep - If 0.0 < T1 < Mult*TimeStep then T1 = Mult*TimeStep
- If 0.0 < T2 < Mult*TimeStep then T2 = Mult*TimeStep
- If 0.0 < T3 < Mult*TimeStep then T3 = Mult*TimeStep
- If 0.0 < Tltr < Mult*TimeStep then Tltr = Mult*TimeStep
- If B <= 0 then B = 0.1
- If Lmax <= 0 then Lmax = 0.1
- If Vmax < Vmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Valve > Vmax, then Vmax = Valve or if Valve < Vmin, then Vmin = Valve
Model Equations and/or Block Diagrams
Parameters:
| MWCap | Turbine Rating, MW |
| R | Permanent droop, pu |
| T1 | Governor mechanism time constant, sec |
| T2 | Turbine power time constant, sec |
| T3 | Turbine exhaust temperature time constant, sec |
| Lmax | Ambient Temperature load limit, pu |
| Kt | Temperature limiter gain |
| Vmax | Maximum turbine power, pu of mwcap |
| Vmin | Minimum turbine power, pu of mwcap |
| Dturb | Turbine damping coefficient, pu |
| Fidle | Fuel flow at zero power output, pu |
| Rmax | Maximum fuel valve opening rate, pu/sec |
| Linc | Valve opening limit, pu |
| Tltr | Valve position averaging time constant, sec |
| Ltrat | Maximum long term fuel valve opening rate, pu/sec |
| A | Turbine power time constant numerator scale factor |
| B | Turbine power time constant denominator scale factor |
| db1pu | Intentional deadband width, pu |
| Err | Intentional db hysteresis, pu |
| db2pu | Unintentional deadband, pu |
| Gv1 | Nonlinear gain point 1, pu gv |
| Pgv1 | Nonlinear gain point 1, pu power |
| Gv2 | Nonlinear gain point 2, pu gv |
| Pgv2 | Nonlinear gain point 2, pu power |
| Gv3 | Nonlinear gain point 3, pu gv |
| Pgv3 | Nonlinear gain point 3, pu power |
| Gv4 | Nonlinear gain point 4, pu gv |
| Pgv4 | Nonlinear gain point 4, pu power |
| Gv5 | Nonlinear gain point 5, pu gv |
| Pgv5 | Nonlinear gain point 5, pu power |
| Ka | Governor gain |
| T4 | Governor lead time constant, sec |
| T5 | Governor lag time constant, sec |